Kinetics™

Acoustical Louvers

Model VAL

Fixed Blade Acoustical Louvers

Kinetics Fixed Blade Acoustical Louvers are economical, effective and attractive. They are designed for maximum sound attenuation when space is limited. They are aesthetically pleasing and available in various material types.

Applications:

Accessories:

Acoustical Louvers are used as part of the intake/exhaust air system of buildings, structures, or equipment to help reduce noise produced by the system equipment. They have a relatively large surface area which compensates for their lack of depth.

Acoustic Performance:

Type Thickness (in.) Noise Reduction* (dB)
125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz
VAL/1 6 5 7 9 10 10 10 12
VAL/2 6 7 11 15 16 17 18 18
VAL/1 12 7 9 13 16 17 18 18
VAL/2 12 8 14 22 27 30 30 31

Aerodynamic Performance:

Type Thickness (in.) Pressure Drop ("W.G.)
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
    Velocity
VAL/1 6 333 471 577 667 745 817 882 943
VAL/2 6 206 292 358 413 462 506 547 585
VAL/1 12 327 462 566 654 731 801 865 925
VAL/2 12 200 283 346 400 447 490 529 566

*Noise Reduction of a louver is the difference between the sound pressure level on the noise source side of the louver and the freefield sound pressure level on the receiver side of the louver.

Standard Sizes: (Width x Height)

2' x 2' 3' x 2' 4' x 2' 5' x 2' 6' x 2'
2' x 3' 3' x 3' 4' x 3' 5' x 3' 6' x 3'
2' x 4' 3' x 4' 4' x 4' 5' x 4' 6' x 4'
2' x 5' 3' x 5' 4' x 5' 5' x 5' 6' x 5'

Note: For larger sizers then listed contact us.

Options

Kinetics Acoustical Louvers are available in aluminum, baked enamal and stainless steel at additional cost.

Specifications

Acoustical Louvers as shown on the contract drawing, or as tabulated shall be installed to reduce sound transmission to occupied areas.

Acoustical Louvers shall be modular, and shall consist of (18ga) steel outer casing and (22ga) perforated steel foil liner, all of which have been mill galvanized.

The acoustical absorption media shall be glass fiber packed under compression. The fiberglass shall be a density caculated to provide the published acoustical and aerodynamic performance, fill material shall be class 1, as tested in accordance with ASTM E-84.

Acoustical Louvers shall be Model VAL.